Model |
|
FEIHCD100S3 |
Type |
|
Monoblock |
Heating conditions: air DB 20℃, domestic water from 15℃ to 55℃ |
|
|
Heating power |
kW |
40,9 |
Input kW (Heating) |
kW |
8,9 |
Heating factor COP |
W/W |
4,6 |
Heating conditions: air DB 12℃, water inlet: 30℃, water outlet: 35℃ |
|
|
Heating power |
kW |
34,1 |
Input kW (Heating) |
kW |
7,1 |
Heating factor COP |
W/W |
4,8 |
Heating conditions: air DB 7℃, water inlet: 30℃, water outlet: 35℃ |
|
|
Heating power |
kW |
32,4 |
Input kW (Heating) |
kW |
7,1 |
Heating factor COP |
W/W |
4,6 |
Heating conditions: air DB 7℃, water inlet: 40℃, water outlet: 45℃ |
|
|
Heating power |
kW |
30,1 |
Input kW (Heating) |
kW |
8,6 |
Heating factor COP |
W/W |
3,5 |
Heating conditions: air DB 2℃, water inlet: 40℃, water outlet: 45℃ |
|
|
Heating power |
kW |
28,5 |
Input kW (Heating) |
kW |
8,9 |
Heating factor COP |
W/W |
3,2 |
Heating conditions: air DB -7℃, water inlet: 40℃, water outlet: 45℃ |
|
|
Heating power |
kW |
25,1 |
Input kW (Heating) |
kW |
9,3 |
Heating factor COP |
W/W |
2,7 |
Cooling conditions: air DB 35℃, water inlet:12℃, water outlet:7℃ |
|
|
Cooling power |
kW |
27,8 |
Input kW |
kW |
9,3 |
Energy Efficiency Ratio EER |
|
3 |
|
|
|
Connection to the power grid |
V / PH / Hz |
380 / 3 / 50 |
Max max. operating electric current |
A |
22,3 |
Noise level |
dB(A) |
56 |
Noise level – Super silent |
dB(A) |
43 |
Water connection – inlet/outlet |
inches |
5/4” |
Water flow – quantity |
m3/h |
4,8 |
ERP level(35℃) |
|
A+++ |
ERP level(55℃) |
|
A++ |
Refrigerant |
|
R32 |
Amount of refrigerant |
kg |
3,5 |
GWP |
|
675 |
Total CO2 equivalent |
t |
2,36 |
Controller |
|
Inventory controller |
Compressor |
|
DC inverter compressor |
Refrigerant flow control |
|
Electric expansion valve |
Heat exchanger |
|
Tubular with slats / Plate |
Product dimensions (w/d/h) |
mm |
1380 / 515 / 1585 |
Weight |
kg |
190 |